Failure of battery charger.

The Enhancement System supervisory signals shall be summarized on a graphic annunciator located near the Fire Alarm Panel using a stand-alone, hardwired annunciator designed to display the supervisory signals described above or, as part of the Fire Alarm graphic annunciator using a delineated area labelled “Radio Enhancement System” containing 3 LEDs; normal operation shall be annunciated with a green LED labelled “Normal” that indicates there are no supervisory signals being sent by the Enhancement System, off normal operation shall be annunciated with a yellow LED labelled “Trouble” that indicates a supervisory signal where the Enhancement System is off normal but still fully operational for in-building radio communications; and system failure shall be annunciated by a yellow LED labelled “Failure” that indicates a supervisory signal that indicates the radio communication performance of the system is unreliable.