Kelowna By-law 10760, s. 9.1.11 — An owner or occupier of premises must ensure that self-contained emergency lighting unit equipment and emergency lights are inspected and tested at intervals not greater than one month to ensure that emergency lights will function upon failure of the primary power supply, and at intervals not greater than 12 months to ensure the unit will provide emergency lighting for a duration equal to the design criterion

Fire and Life Safety Bylaw

Last checked

Indexed text

An owner or occupier of premises must ensure that self-contained emergency lighting unit equipment and emergency lights are inspected and tested at intervals not greater than one month to ensure that emergency lights will function upon failure of the primary power supply, and at intervals not greater than 12 months to ensure the unit will provide emergency lighting for a duration equal to the design criterion.