London By-law CP-24, s. 4.8.5 — Headroom – Heights The minimum floor to ceiling headroom for habitable space shall
Last checked
Indexed text
Headroom – Heights The minimum floor to ceiling headroom for habitable space shall:
- a) not be less than 1.95 m (6 ft 5
- in) over the floor area and in any location that would normally be used as a means of egress; or
- b) not be less than 1.95 m (6 ft 5
- in) over at least 50% of the floor area, provided that any part of the floor having a clear height of less than 1.4 m (4 ft 7
- in) shall not be considered in computing the floor area. However, a minimum height of 1.95 m (6 ft 5
- in) shall be required for all floor area used as a means of egress. As of January 1, 2025 The minimum floor to ceiling headroom for habitable space shall:
- a) not be less than 1.85 m (6 ft 1
- in) over the floor area and in any location that would normally be used as a means of egress; or
- b) not be less than 1.85 m (6 ft 1
- in) over at least 50% of the floor area, provided that any part of the floor having a clear height of less than 1.4 m (4 ft 7
- in) shall not be considered in computing the floor area. However, a minimum height of 1.85 m (6 ft 1
- in) shall be required for all floor area used as a means of egress.
Short excerpt. The rest of the text is on the official source.
Official source · Table of contents
Topics
Related sections
- 4.8.3
- 4.8.4
- 4.8.5.1 Headroom – Height exceptions Minimum floor to ceiling headroom for habitable space shall follow provisions in 4.8.5, with the following exceptions
- 4.8.6 Ventilation – Provided – Maintained Every habitable room except for a living room and a dining room shall be provided and maintained with natural ventilation which shall