Emergency lighting shall be provided to an average level of illumination not less than 10 lux at floor or tread level in:
- [1] Exits;
- [2] Principal routes providing access to exit in an open floor area and in service rooms;
- [3] Corridors used by the public;
- [4] Corridors serving patients' or residents' sleeping rooms in a care and treatment occupancy or care occupancy;
- [5] Corridors serving classrooms;
- [6] Underground walkways;
- [7] Public corridors;
- [8] Floor areas or parts of them where the public may congregate in assembly occupancies intended for the production and viewing of the performing 629-37 April 30, 2025 arts or other assembly occupancies, having an occupant load of 60 or more, other than arena-type or open-air assembly occupancies;
- [9] Floor areas or parts of them in day-care centres where persons are cared for;
- [10] Food preparation areas in commercial kitchens;
- [11] Principal routes providing access to exit in a floor area that is not subdivided into rooms or suites of rooms served by corridors in a business and personal services occupancy, a mercantile occupancy or an industrial occupancy;
- and [12] Internal corridors or aisles serving as principal routes to exits in a business and personal services occupancy, a mercantile occupancy or an industrial occupancy that is subdivided into rooms or suites of rooms, and is not served by a public corridor.
Short excerpt. The rest of the text is on the official source.
Official source · Table of contents
Topics
Related sections
Other cities
To report a correction: info@bylawinsider.com. This link opens your mail program.
Unofficial copy for convenience; the official version governs. Official source
Short excerpts only. The official PDF on toronto.ca governs.