Windsor By-law 148-2025, s. 5.2.42(a) — Parking Garage & Parking Structures Requirements Parking garages and parking structures shall be

Last checked

Indexed text

Parking Garage & Parking Structures Requirements Parking garages and parking structures shall be:

  • maintained in a clean, structurally sound, free from defects and safe condition;
  • (b) adequately ventilated at all times to provide (3.8L/s/m²) of floor area minimum if ventilated by mechanical means unless the system is controlled by a Carbon Monoxide detection system;
  • (c) the ventilation systems referenced in sentence
  • (b) shall be maintained in proper working order, free from defects;
  • (d) where the officer has doubts to the effectiveness of the ventilation and/or carbon monoxide detection system, can at the

owners expense order testing to confirm compliance with sentence (b);

  • (e) adequately lighted at all times, so that the number and arrangement of light fixtures is such as to provide an average level of illumination of at least 54 lux at floor level over the entire floor area with a minimum level of 11 lux at any location on the floor;
  • (f) equipped with wire screens or other suitable means of protection for lighting fixtures, so as to prevent accidental or malicious damage; and
  • (g) shall be provided with an effective fire separation and barrier to the passage of gas and exhaust fumes from any part of the parking garage into any other part of the building used or intended to be used for human occupancy.