Kelowna : Règlement no 10760, art. 5.3.3(i) — The confirmation referred to in Section 5.3.2 shall be in a form acceptable to the Fire Inspector and shall identify, without limitation
Fire and Life Safety Bylaw
Vérifié le
Texte indexé
The confirmation referred to in Section 5.3.2 shall be in a form acceptable to the Fire Inspector and shall identify, without limitation:
- occupancy hazard or commodity classification,
- (ii) method of packaging and encapsulation,
- (iii) method of storage of commodities (e.g. by rack, palletized, solid pile, solid shelving),
- (iv) height of storage, and
- (v) clearance between racks, piles or stacks;
- d) The required level of manual firefighting equipment (e.g. fire hose and portable fire extinguishers);
- e) The required and available density of water application;
- f) The required design area of water application;
- g) The fire alarm system and central station connection(s); and
- h) A statement of the current status and level of performance of the sprinkler system, including whether the sprinkler system conforms or does not conform to the identified design standard, and if nonconforming, provide specific instructions for the improvement of the sprinkler system, reduction of the fuel load or other alternative solutions acceptable to the Fire Inspector.
Extrait court. Le reste du texte est sur la source officielle.
Source officielle · Table des matières
Sujets
Articles voisins
- 5.3.2 Where a Fire Inspector considers that a change in the use or occupancy of a building equipped with a sprinkler system may create an increased fire hazard, such that the use or occupancy exceeds the criteria for which the sprinkler system was designed, the Fire Inspector may require the owner or occupier to provide confirmation to the Fire Inspector by a professional engineer that the design limitations of the original sprinkler system installation standard have not been exceeded
- 5.3.3 The confirmation referred to in Section 5.3.2 shall be in a form acceptable to the Fire Inspector and shall identify, without limitation
- 5.3.4 Fire sprinkler isolation valves shall be installed so that they are readily accessible
- 5.3.5 Fire sprinkler control valves and/or fire sprinkler “trees” shall not be installed in a location which is obstructed by adjacent mechanical systems. An unobstructed access of 1m shall be provided in front of each control valve and a center line radius of 50 cm on either side of the control valve
Autres villes
Pour signaler une correction : info@bylawinsider.com. Ce lien ouvre votre programme de courriel.
Copie non officielle, pour faciliter la lecture. La version officielle prévaut. Source officielle
Short excerpts of a public bylaw PDF. The official PDF governs.