Without limiting Section 5.8.4, the owner of property on which a private fire hydrant is installed must:

  • a) once a year, have the private hydrant flushed and drained and have all the threads of outlets and caps greased with waterproof grease;
  • b) retain service records for two years and provide to the Fire Chief or designate when requested;
  • c) provide the Fire Chief or designate with a written report of the flow test performed on new or relocated fire hydrants in accordance to NFPA 291 on a form approved by the AHJ. A combination of actual flow and modeling is acceptable;
  • d) ensure fire hydrant colour coding is based on NFPA 291 Standards; and
  • e) ensure a fire hydrant has a weatherproof service ring indicating the service date and volume installed on the 65 mm port. The ring must be larger than cap. BL11116, BL11747 & BL12869 amended Section 5.9: