Nanaimo : Règlement no 7108, art. 34(a) — 34 Semi-Annually Inspection The owner of a Private Hydrant is responsible to conduct or have conducted the following minimum inspection requirements semi-annually

Fire Protection and Life Safety Regulation Bylaw

Vérifié le

Texte indexé

34 Semi-Annually Inspection The owner of a Private Hydrant is responsible to conduct or have conducted the following minimum inspection requirements semi-annually:

  • examine the exterior for broken, cracked or missing parts;
  • (b) check to ensure that the hydrant hose ports are the proper elevation and facing a direction for the most efficient use;
  • (c) check to ensure that the hydrant is not obstructed by tall grass, shrubbery or other items;
  • (d) check for worn, rusted or obstructed threads which may hamper efficient use;
  • (e) inspect hydrant barrels to determine if water has been accumulated as a result of leaking main valve, plugged or damaged drain valve;
  • (f) check for non-drainage of hydrant, leakage past valve seat, plugged drains; and,
  • (g) after winter, the hydrant should be checked for damage caused by frost, ground heave, snow, road salt or sand.

Extrait court. Le reste du texte est sur la source officielle.

Source officielle · Table des matières

Pour signaler une correction : info@bylawinsider.com. Ce lien ouvre votre programme de courriel.

Copie non officielle, pour faciliter la lecture. La version officielle prévaut. Source officielle

Short excerpts of a public bylaw PDF. The official PDF governs.