Aurora : Règlement no 6543-23, art. 27.3(a) — Property Standards By-law
Property Standards By-law
Vérifié le
Texte indexé
an exit, a public corridor, a corridor providing access to exit for the public,
a corridor serving patients or residents in a care and treatment occupancy or care occupancy, a corridor serving classrooms, an electrical equipment room, a transformer vault and a hoistway pit shall be equipped to provide illumination to an average level not less than 50 lux at floor or tread level and at angles and intersections at changes of level where there are stairs or ramps;
- (b) elevator machine rooms shall be equipped to provide illumination to an average level of not less than 100 lux at floor level;
- (c) for parking lots, walkways, stairs, porches, verandas, loading docks, ramps or other similar areas, a minimum level of illumination of 10 lux at ground or tread level and at angles and intersections at changes of level where there are stairs or ramps;
- (d) emergency lighting shall be provided in:
- (i) exits,
- (ii) principal routes providing access to exit in an open floor area and in service rooms,
- (iii) corridors used by the public,
- (iv) corridors serving classrooms,
- (v) underground walkways,
- (vi) public corridors,
- (vii) floor areas or parts of them where the public may congregate in, By-law Number 6543-23
- (viii) floor areas or parts of them in day care centres where persons are cared for,
- (ix) food preparation areas in commercial kitchens,
- (x) principal routes providing access to exit in a floor area that is not subdivided into rooms or suites of rooms served by corridors in
a business and personal services occupancy, a mercantile occupancy or an industrial occupancy,
- (xi) internal corridors or aisles serving as principal routes to exits in
a business and personal services occupancy, a mercantile occupancy or an industrial occupancy that is subdivided into rooms or suites of rooms, and is not served by a public corridor,
- (xii) washrooms with fixtures for public use, and
- (xiii) any other occupancies and corridors as required under the Building Code.
Extrait court. Le reste du texte est sur la source officielle.
Source officielle · Table des matières
Sujets
Articles voisins
- 27.2(a) The emergency lighting required in paragraph
- 27.3 Within all buildings exceeding three storeys in building height or having a building area exceeding 600 square metres or used for other occupancies not described in subsection 27.1
- 27.4 The emergency lighting required in paragraph
- 27.5 All interior lighting installed to provide the minimum level of illumination required by this by-law may be on circuits controlled by motion sensor-controlled switches, except where the lighting circuit is for an exit, including an exit stairway, or for emergency lighting
Autres villes
Pour signaler une correction : info@bylawinsider.com. Ce lien ouvre votre programme de courriel.
Copie non officielle, pour faciliter la lecture. La version officielle prévaut. Source officielle
Short excerpts of a public bylaw PDF. The official PDF governs.