Kelowna : Règlement no 10760, art. 2.3 — Description of Interior Building Coverage Requirements Reliable two-way radio communications shall be achieved in the following areas and locations inside the building
Fire and Life Safety Bylaw
Vérifié le
Texte indexé
Description of Interior Building Coverage Requirements Reliable two-way radio communications shall be achieved in the following areas and locations inside the building:
- Table 1 Floor Area for Reliable Communications Floor Area for Reliable Two-Way Location Radio Communications
Extrait court. Le reste du texte est sur la source officielle.
Source officielle · Table des matières
Sujets
Articles voisins
- 3.4 has been measured by the U.S. Department of Commerce, National Telecommunications and Information Administration to be approximately equivalent to 16 dB signal to noise and distortion ratio for ETSI DMR 2-slot signals. It may also be approximately equivalent to a received signal level of -95 dBm, including allowances for portable antenna gain and body losses, in the absence of other signals that may affect the receiver
- 2.2 Certified and Desing Signal Strength Thresholds Following the complete construction of the building interior including all exterior and interior walls and all doors and windows installed minimum certified signal strength of -95 dBm shall be obtained in all floor areas as per Table 1
- 1 Public access hallways, elevator lobbies 95% of each area on each floor
- 2 Living areas 95% of each enclosed area within each living area
Autres villes
Pour signaler une correction : info@bylawinsider.com. Ce lien ouvre votre programme de courriel.
Copie non officielle, pour faciliter la lecture. La version officielle prévaut. Source officielle
Short excerpts of a public bylaw PDF. The official PDF governs.