Stairs – Interior – Single Unit Dwelling The stair tread rise and run for residential interior single dwelling unit shall not exceed the following unless existing acceptable to the Officer:
- (i) Maximum rise 210 mm
- (ii) Minimum tread 230 mm
- (iii) Minimum run 200 mm
- (iv) If run is less than 240 mm, a 25 mm nosing is required
- (b) Stairs – Residential – Not Within
- (i) Maximum rise 210 mm
- (ii) Minimum tread 240 mm
- (iii) Minimum run 212 mm
- (iv) If run is less than 240 mm, a 25 mm nosing is required
- (b) Stairs – Non-residential
- (i) Rise minimum 125 mm, maximum 200 mm
- (ii) Minimum run of 230 mm, must be uniform
- (iii) If run is less than 240 mm, a 25 mm nosing is required
- (iv) Existing winders of not more than 3 in 90 degrees and not more than 1 set between floors are permitted and where each tread is not less than 30 degrees and each tread is not greater than 45
- (c) Stairs – Service Rooms – curved/spiral Stairs may exceed the requirements in 1.13
- (c) if serving only service rooms, service spaces and other rooms unused in industrial occupancies serving equipment and machinery, or existing curved and spiral stairs in dwelling units acceptable to the officer.
Extrait court. Le reste du texte est sur la source officielle.
Source officielle · Table des matières
Sujets
Articles voisins
- 5.2.12 Openings in Guards Guard – Openings Guards for residential occupancies shall have no openings which would permit the passage of a spherical object having a diameter of 100 mm unless it can be shown that the location and size of such openings which exceed this limit does not represent a hazard
- 5.2.13 Stair Requirements Stairs
- 5.2.14 Roofs, Chimneys, Fascia, Soffit, Antennas, Solar Panels All roofs, including chimneys, stacks, masts, lightning arresters, antennas, fascia, soffits, flashings, solar panel and supports, and other roof structures shall be maintained in good repair, watertight and structurally sound condition. Such maintenance may include, but is not limited to
- 5.2.15 Eaves Troughs Water runoff from roof surfaces shall discharge into an eaves trough or gutter and thence to a downpipe, discharging directly to grade with an appropriate extension away from the building to prevent flooding, erosion and other nuisance to neighboring properties
Autres villes
Pour signaler une correction : info@bylawinsider.com. Ce lien ouvre votre programme de courriel.
Copie non officielle, pour faciliter la lecture. La version officielle prévaut. Source officielle
Short excerpts of a public bylaw PDF. The official PDF governs.